[SystemSafety] Separating critical software modules from non-critical software modules

Ignacio González (Eliop) igtorque.eliop at googlemail.com
Wed Jul 24 12:07:53 CEST 2013


Peter, I come from the railway world. In nuclear, you cannot even use an OS
with safe partitioning, Arinc-style, hypervisors, etc.?



2013/7/24 Peter Bishop <pgb at adelard.com>

> With no physical separation you need to be very sure that "non-safety"
> cannot affect safety (overwriting "safe" memory, crashing the system,
> hogging cpu, comms...)
> In nuclear standards, anything in the same box has to be implemented to
> the level of the most critical function.
>
> Peter Bishop
>
>
> On 24 July 2013 09:29, Gerry R Creech <grcreech at ra.rockwell.com> wrote:
>
>> Malcolm,
>>
>> I agree that for small devices it may be difficult to provide or prove
>> separation between safety and non-safety and therefore all needs to be
>> considered safety in these cases.
>>
>> However, I am also a firm believer that removing complexity increases
>> safety. If I can prove, say 50% of the code, cannot affect safety then I
>> can focus on the 50% that does and not get distracted on the areas that
>> have less effect.
>>
>> Just because there is a safety & non-safety section, doesn’t mean that
>> the programming style needs to be different, after all even in the
>> non-safety section quality is important for any product and the non-safety
>> sections obviously need to be in the document structure clearly documented
>> as non-safety.
>>
>> Once the segregation is in place it has several benefits, for example,
>> although all code needs to be reviewed & tested (from a quality point of
>> view) why focus on software that could be classed as black channel software
>> components where the safety aspect is assured elsewhere, the focus can be
>> where it is needed, complexity is reduced and the amount of important
>> safety code is reduced.
>>
>> This method has the added benefit that proven in use / COTS firmware can
>> be used in the non-safety area knowing that it is unlikely to affect the
>> safety firmware.
>>
>>
>> Best regards,
>>
>> Gerry Creech
>>
>>
>>
>>
>> From:        "Watts Malcolm (AE/ENG11-AU)" <Malcolm.Watts at au.bosch.com>
>> To:        "systemsafety at TechFak.Uni-Bielefeld.DE" <
>> systemsafety at TechFak.Uni-Bielefeld.DE>
>> Date:        24/07/2013 02:01
>> Subject:        Re: [SystemSafety] Separating critical software modules
>> from non-critical software modules
>> Sent by:        systemsafety-bounces at lists.techfak.uni-bielefeld.de
>> ------------------------------
>>
>>
>>
>> Our exerience in automotive is that it is effectively impossible for most
>> automotive products to have the kind of separation José speaks of; for
>> example “two separate board groups”.  Much of our software (although not
>> SIL4 – often SIL2 equivalent) runs on a single micro in a single device.
>>  Very high integrity product might have 2 independent micros in a single
>> enclosure, with some redundancy of function in other devices in the vehicle
>> (for example, data redundancy). Many of the micros used do not have
>> memory-protection units, and micros may be running only scheduling
>> executives, not full operating systems (in the interests of simplicity,
>> proven field use, and testability).  In this circumstance, it makes the
>> most sense (to me) to develop all of the software in the micro to the
>> highest integrity level required by any component.
>>
>> I share the concerns raised in to Myriam’s post; as a matter of
>> practicality, few developers are feasibly able to swap back and forth
>> between “safety” and “no-safety” development methodologies (to say nothing
>> of the cost and complexity of maintaining two sets of procedures, two sets
>> of training, duplicated QA, the complexity of planning and tracking, and so
>> on.  To answer Myriam’s rhetorical question; no, for me it does not make
>> sense that developers can swap back and forward between two different
>> mindsets without mistakes, and no, it does not make much sense that
>> tightly-coupled modules can be part of significantly different lifecycles
>> without adverse effects on interfaces, assumptions, change management and
>> quality requirements.  [This is the same problem faced when incorporating 3
>> rd-party components. There’s a reason that such a high proportion of
>> defects are in the interfaces].
>>
>> The more conservative approach (taking into account possible changes, and
>> mistakes in understanding whether a component or its interface is
>> safety-relevant or not, under given circumstances, is to develop all
>> software components (in tightly-coupled products typical of automotive) to
>> the highest-applicable integrity level.
>>
>> The benefit you get (in my opinion) is reduced risk due to unexpected
>> interference between modules, reduce risk due to systematic defects,
>> reduced risk due to human-factors effects from the developers, reduced cost
>> due to consistency, and better/faster impact analysis on change.
>>
>> The flip side is increased cost and effort for all components (and their
>> integration ?) that could otherwise have been considered
>> “non-safety-relevant”.  This really is a serious disadvantage of the
>> approach.  Ignacio mentioned that this may be practical only for small
>> teams and “small software”.  Does anyone know of any research in this area ?
>>
>> Best Regards,
>>
>> Mal.
>> Mal Watts
>>
>> --------------------------------------------------------------------------------------------------------------
>> Functional Safety Manager (AE/ENG11-AU)
>> Robert Bosch (Australia) Pty. Ltd.
>> Automotive Energy and Body Systems,
>> Locked Bag 66  - Clayton South, VIC 3169  -  AUSTRALIA
>> Tel: +61 3 9541-7877            Fax: +61 3 9541-3935
>> Malcolm.Watts at au.bosch.com     * **www.bosch.com.au*<http://www.bosch.com.au>
>>
>> *From:* systemsafety-bounces at lists.techfak.uni-bielefeld.de [
>> mailto:systemsafety-bounces at lists.techfak.uni-bielefeld.de<systemsafety-bounces at lists.techfak.uni-bielefeld.de>]
>> *On Behalf Of *José Faria*
>> Sent:* Tuesday, 23 July 2013 7:58 PM*
>> To:* M Mencke*
>> Cc:* systemsafety at techfak.uni-bielefeld.de*
>> Subject:* Re: [SystemSafety] Separating critical software modules from
>> non-critical software modules
>>
>> Myriam,
>>
>> Yes, it is a valid approach. Valid meaning both technically feasible and
>> acceptable by certification authorities. As Gerry said, the fundamental
>> issue is to demonstrate that the lower SIL level part cannot compromise the
>> higher level part.
>>
>> In the systems I've worked the basic architecture solution was to have 2
>> separate board groups for the SIL4 and SIL0 software. In such a solution,
>> you can find the guidance for the safety analysis of the communication
>> protocol between the two boards in EN 50159 Annex A.
>>
>> Best,
>> José
>>
>> On Tue, Jul 23, 2013 at 9:21 AM, M Mencke <*menckem at gmail.com*<menckem at gmail.com>>
>> wrote:
>>
>> Dear All,
>>
>> For any software development project, many software modules are involved,
>> where some are defined as safety critical, others are not. For example, in
>> railway signaling, communications modules are likely to be defined as
>> critical, whereas other modules such as those involving data storage or
>> other basic functions are not. An analysis may be performed with the
>> objective of demonstrating that the safety critical modules are entirely
>> independent from the non critical modules, leading to the conclusion that
>> the application of a programming standard for safety critical software is
>> only required for those modules defined as safety critical (note the phrase
>> “with the objective of demonstrating…”; I would hesitate before drawing the
>> conclusion that the analysis really demonstrates what it is supposed to
>> demonstrate).
>>
>> In my field the EN 50128 would be applied, however, it could be any
>> standard for safety critical software. Thus, the software is developed
>> applying the standard only to the modules which have been defined as
>> “safety critical”. In order to supposedly save time/money, etc., the rest
>> of the modules are developed as non-critical software, either as SIL 0
>> functions or according to a standard programming standard. My question is
>> whether such an approach is really valid, given that the application of a
>> safety critical standard does not only involve the application of specific
>> language features, it involves an entire development life cycle, and I find
>> it difficult to see how the modules defined as “non-critical” then do not
>> form part of that life cycle. I’m not saying it is not valid, but I would
>> like to know how others see this.
>>
>> Additionally, if the same programmers are involved in the programming of
>> both critical and non-critical modules, does it really make sense that they
>> only pay attention to the features required for safety critical software
>> when programming the critical modules, and modify their programming style
>> for the rest of the modules (or revert back to their “usual” style)? These
>> questions also depend on what you consider as critical, for example, for a
>> control system with a HMI, you could only consider communication modules
>> critical, however, you need a GUI to display the status of the elements an
>> operator has to control correctly. Some operations performed by the
>> operator may not have the potential to generate a hazard with a high
>> severity level, because there are mitigations in place. However, that
>> doesn’t necessarily mean that the software responsible for displaying the
>> information should not be programmed according to a safety critical
>> standard. I am aware that these questions don’t have an “easy” answer; any
>> opinions would be appreciated.
>>
>> Kind Regards,
>>
>> Myriam.
>>
>> _______________________________________________
>> The System Safety Mailing List*
>> **systemsafety at TechFak.Uni-Bielefeld.DE*<systemsafety at TechFak.Uni-Bielefeld.DE>
>>
>>
>>
>> --
>> --
>> *José Miguel Faria*
>> *Educed *- Engineering made better
>> t: +351 913000266
>> w: *www.educed-emb.com* <http://www.educed-emb.com/>
>> e: *jmf at educed-emb.com* <jmf at educed-emb.com>
>>  _______________________________________________
>> The System Safety Mailing List
>> systemsafety at TechFak.Uni-Bielefeld.DE
>>
>>
>> _______________________________________________
>> The System Safety Mailing List
>> systemsafety at TechFak.Uni-Bielefeld.DE
>>
>>
>
> _______________________________________________
> The System Safety Mailing List
> systemsafety at TechFak.Uni-Bielefeld.DE
>
>